Walk-in cooler compressor replacement on a café rooftop — Aurora

A café in Aurora lost cooling in its walk-in cooler. Diagnosis on the roof found a failed scroll compressor in the condensing unit. We replaced the compressor and liquid-line filter-drier, pulled a deep vacuum, recharged the system and verified temperatures, pressures and amperage at start-up.

Equipment: Walk-in cooler with a Larkin evaporator and a rooftop Heatcraft condensing unit with a Copeland Scroll compressor

New scroll compressor installed in the condensing unit

The problem

The walk-in cooler is served by a Heatcraft condensing unit on the roof, with a Larkin evaporator inside the box. The compressor had failed, and the connections around it showed oil and burn marks.

A compressor replacement is a sealed-system repair: the refrigerant has to be recovered before anything is opened, and the system has to be cleaned up properly so the new compressor does not fail the same way. That work is done by EPA Section 608 certified technicians.

What we did

  1. Diagnosed the system and inspected the electrical side to find the cause of the compressor failure.
  2. Recovered the existing refrigerant from the system.
  3. Removed the failed compressor and installed a new scroll compressor.
  4. Replaced the liquid-line filter-drier, and replaced compressor oil where required.
  5. Pulled a deep vacuum on the refrigeration system and leak-checked it under pressure.
  6. Recharged the system with new refrigerant.
  7. Started the unit and verified system pressures, temperatures and compressor amperage, then ran a final performance check and cleaned up.
Photos from the job

On site

Result

The walk-in cooler was back in service with the new compressor running. Temperature checks after start-up read in the mid-to-high 30s °F inside the box, below the 41°F cold-holding limit.

Takeaway for operators

When a compressor fails, the cause matters as much as the part. Electrical inspection, a new filter-drier and a deep vacuum protect the new compressor — skipping them is how a second compressor fails a few months later.