Danfoss ERC Controller Alarm Codes

Electronic refrigeration controllers used on bottle coolers, reach-ins and display cabinets. Covers: ERC 211, ERC 213, ERC 214 (ERC 21x series)

Commercial service call$129
Waived when you approve the repairWritten quote before any work · same- or next-day appointments · 90-day warranty on parts and labor

How the codes appear

The display alternates between the air temperature and the active alarm/error code; an alarm bell icon lights.

Resetting

Alarms show until the condition is resolved. A61 clears when condenser temperature drops 5 K below the limit. A80 needs a manual reset: set r12 to OFF and back ON, or power the controller down.

If the same code comes back after a reset, stop resetting it — repeated restarts can hide the real fault or damage components. Call a technician.

Danfoss code list

E27

Defrost sensor error

Technician

The evaporator (defrost) sensor is faulty or disconnected.

Causes the manufacturer lists

  • Defective or disconnected evaporator sensor
E29

Air sensor error

Technician

The cabinet air temperature sensor is faulty or disconnected.

Causes the manufacturer lists

  • Defective or disconnected air sensor

What staff can safely check

  • Check the cabinet with a separate thermometer
E30

Condenser sensor error

Technician

The condenser temperature sensor is faulty or disconnected.

Causes the manufacturer lists

  • Defective or disconnected condenser sensor
A01

High temperature alarm

Status / staff can check

Cabinet air temperature is too high.

What staff can safely check

  • Close the door fully
  • Don't overload the cabinet or block air vents
A02

Low temperature alarm

Status / staff can check

Cabinet air temperature is too low.

What staff can safely check

  • Check product for freezing
A04

Door alarm

Status / staff can check

The door has been open too long.

Causes the manufacturer lists

  • Door left open

What staff can safely check

  • Close the door and check nothing is blocking it
A15

DI alarm

Technician

An external alarm signal has been received on a digital input.

A45

Standby alarm

Technician

Control has been stopped with the main switch setting (r12), so the unit is not cooling.

Causes the manufacturer lists

  • Controller main switch set to OFF
A61

Condenser alarm

Technician

Condenser temperature is too high; the manual says to check airflow.

Causes the manufacturer lists

  • Poor airflow over the condenser

What staff can safely check

  • Clear boxes or items blocking the condenser grille
A80

Condenser block alarm

Technician

Condenser temperature has gone too high and the controller has locked out; a manual reset is required.

Causes the manufacturer lists

  • Condenser overheating

What staff can safely check

  • Clear anything blocking the condenser grille
A99

High voltage alarm

Technician

Supply voltage is too high; compressor protection is active.

Causes the manufacturer lists

  • Supply voltage too high
AA1

Low voltage alarm

Technician

Supply voltage is too low; compressor protection is active.

Causes the manufacturer lists

  • Supply voltage too low

What staff can safely check

  • Make sure the unit is not on an extension cord or overloaded circuit

Seeing Danfoss codes you can't clear?

Same- or next-day appointments across the Denver metro. Written quote before any work, EPA 608 certified technicians.

Request service

Model notes

Other displays: -d- defrost in progress, Pud pull-down, Err temperature can't be shown due to sensor error, Loc/UnL keypad locked/unlocked, OFF control stopped. Danfoss EKC models use different codes and are not covered here.

Sources

Compiled and paraphrased from the manufacturer documents above. Codes differ between model years and control boards — confirm against the manual for your exact model. ABC Denver Appliance Repair is an independent service company, not affiliated with Danfoss.

From our job records

Photos from our job records

Real photos our technicians took on calls around Denver and the Front Range. Each caption says what was done; no customer details are shown.

Thermador double wall oven
Thermador double wall oven
GE Monogram dispenser after the water valve and ice maker were replaced
GE Monogram dispenser after the water valve and ice maker were replaced
Whirlpool heat pump dryer after the service
Whirlpool heat pump dryer after the service
Dishwasher in an Arvada kitchen during a combined dishwasher and range call
Dishwasher in an Arvada kitchen during a combined dishwasher and range call

Call (720) 534-0432