Hoshizaki Ice Machine Alarm Codes (KM Series)

Modular crescent cube ice machines (KM / KMD series). Covers: Current Hoshizaki modular crescent cubers; the same 1/2/3/6/7 alarm set appears on the earlier 'G' control board used on larger modular cubers_H models

Commercial service call$129
Waived when you approve the repairWritten quote before any work · same- or next-day appointments · 90-day warranty on parts and labor

How the codes appear

The control board sounds a repeating audible alarm (the number of beeps identifies the alarm; on the G board the beeps repeat every 3 seconds) and the machine shuts down. Voltage problems are flagged by the red POWER OK LED going out rather than a manual reset alarm.

Resetting

Alarms 1-3: press the ALARM RESET button on the control board with power on. Voltage alarms (6 and 7) reset automatically once voltage is corrected. The manual cautions that pressing OUTPUT TEST while the board is in alarm starts an output test and locks out ALARM RESET until power is cycled off and on.

If the same code comes back after a reset, stop resetting it — repeated restarts can hide the real fault or damage components. Call a technician.

Hoshizaki code list

1 beep

High evaporator temperature

Technician

The evaporator thermistor read above about 127°F (53°C), which points to a harvest problem or hot conditions at the evaporator. The machine shuts down until it is manually reset.

Causes the manufacturer lists

  • Hot gas valve or its relay stuck on
  • Hot water entering the unit
  • Headmaster (head pressure valve) stuck
  • Shorted thermistor
2 beeps

Harvest backup timer

Technician

Harvest ran longer than 20 minutes on two cycles in a row, so the board stopped the machine. Requires a manual reset.

Causes the manufacturer lists

  • Open (failed) thermistor
  • Hot gas valve not opening
  • TXV or liquid line valve leaking by
  • Low refrigerant charge
  • Inefficient compressor
  • Water regulating valve leaking by (water-cooled)
3 beeps

Freeze timer

Technician

The freeze cycle ran longer than the board's freeze timer setting on two cycles in a row, so the board stopped the machine. Requires a manual reset.

Causes the manufacturer lists

  • Float switch stuck closed
  • Inlet water valve leaking by
  • Hot gas valve leaking by
  • Water pump not pumping
  • Defective TXV
  • Liquid line valve not opening
  • Low refrigerant charge
  • Headmaster not bypassing
  • Inefficient compressor
6 (low voltage)

Low voltage

Technician

Control voltage dropped to roughly 92 VAC (±5%) or less. The red POWER OK LED goes out while this protection is active, and the machine restarts on its own once voltage is back to normal.

Causes the manufacturer lists

  • Low control/supply voltage

What staff can safely check

  • Confirm the machine's breaker has not tripped and power is on (the manual's basic check for no power: blown fuse, tripped breaker, loose connection)
7 (high voltage)

High voltage

Technician

Control voltage rose to roughly 147 VAC (±5%) or more; the board cuts out within about 3 seconds and restarts automatically when voltage returns to normal.

Causes the manufacturer lists

  • Incorrect wiring (the manual notes single-phase 3-wire models in particular)

Seeing Hoshizaki codes you can't clear?

Same- or next-day appointments across the Denver metro. Written quote before any work, EPA 608 certified technicians.

Request service

Model notes

Official tables show alarm numbers 1, 2, 3, 6 and 7 only (4 and 5 are not used on these boards; older 'E' boards on some 2006-era models used 4 = short circuit and 5 = open circuit in the K4/bin control harness). The manual gives the freeze timer as adjustable (dip switches; 50/60/70 min on the G board). Newer boards also blink the POWER LED for freeze-time correction / freeze-up detection; those are informational, not beep alarms. Hoshizaki states that service should be done by qualified technicians. The manuals' general user items (not tied to a specific alarm): water supply shut-off valve open and filters/screens not clogged, ambient 45-100°F, 6 in. clearance at rear, sides and top, clean condenser/air filter. IM/AM series were not researched.

Sources

Compiled and paraphrased from the manufacturer documents above. Codes differ between model years and control boards — confirm against the manual for your exact model. ABC Denver Appliance Repair is an independent service company, not affiliated with Hoshizaki.

From our job records

Photos from our job records

Real photos our technicians took on calls around Denver and the Front Range. Each caption says what was done; no customer details are shown.

Whirlpool stacked washer and dryer in a Golden laundry closet
Whirlpool stacked washer and dryer in a Golden laundry closet
Dryer opened up for a drive motor replacement in Mead
Dryer opened up for a drive motor replacement in Mead
Thermometer check in a Bosch refrigerator freezer with a stopped ice maker
Thermometer check in a Bosch refrigerator freezer with a stopped ice maker
Water inlet valves on an LG washer during a valve replacement in Arvada
Water inlet valves on an LG washer during a valve replacement in Arvada

Call (720) 534-0432