Walk-in cooler and freezer refrigeration systems (Heatcraft, also sold under Bohn, Larkin, Climate Control, Chandler brands). Covers: Beacon II board / Beacon II Refrigeration System

Commercial service call$129
Waived when you approve the repairWritten quote before any work · same- or next-day appointments · 90-day warranty on parts and labor

How the codes appear

Shown on the red three-digit LED display on the Beacon II board in the evaporator. Alarms also close a dry alarm contact that can drive a light, buzzer or bell.

Resetting

A1 and A2 clear automatically when box temperature returns inside the setpoints. A3 clears by putting the system in Service Mode or turning off power. E1, E3, E4 keep the system off until the fault is cleared or the breaker is reset.

If the same code comes back after a reset, stop resetting it — repeated restarts can hide the real fault or damage components. Call a technician.

Heatcraft code list

A1

High box temperature

Status / staff can check

Room temperature stayed above the high alarm setpoint for the alarm time (default 60 minutes). Not checked during defrost.

What staff can safely check

  • Make sure the walk-in door closes and seals fully
  • Check strip curtains and that the door isn't propped open
A2

Low box temperature

Technician

Room temperature stayed below the low alarm setpoint for the alarm time.

What staff can safely check

  • Check product for freezing
A3

System start-up failure

Technician

The compressor failed to start after 4 attempts (it retries every 4 minutes and keeps trying).

Causes the manufacturer lists

  • Pressure safety switch (high, low or oil) open - see E7

What staff can safely check

  • Move product if the box is warming
A4

Input fault

Technician

Box temperature sensor, suction temperature sensor or pressure transducer is open or not installed.

Causes the manufacturer lists

  • Faulty sensor or transducer
E1

Room temperature sensor fault

Technician

Room sensor is shorted, open or not installed. The system pumps down and stays off until the fault is cleared.

Causes the manufacturer lists

  • Sensor or its board connection

What staff can safely check

  • Move product to other refrigeration
E2

Defrost temperature sensor fault

Technician

Defrost sensor is shorted, open or not installed.

Causes the manufacturer lists

  • Sensor or its board connection
E3

Suction temperature sensor fault

Technician

Suction temperature sensor is shorted, open or not installed. System pumps down and stays off.

Causes the manufacturer lists

  • Sensor or its board connection
E4

Suction pressure transducer fault

Technician

Suction pressure transducer is shorted, open or not installed. System pumps down and stays off.

Causes the manufacturer lists

  • Transducer or its board connection
E5

Outdoor temperature sensor fault

Technician

Outdoor temperature sensor is shorted.

Causes the manufacturer lists

  • Sensor or wiring
E6

Low superheat

Technician

Superheat stayed at 0°F for 2 minutes during cooling.

Causes the manufacturer lists

  • Wrong refrigerant setting on board
  • Iced coil / defrost problem
  • Expansion valve (EEV) problem
  • Low pressure switch setting
  • Sensor or transducer reading wrong

What staff can safely check

  • Report any heavy ice build-up on the evaporator coil
E7

Compressor shutdown

Technician

A high-pressure, low-pressure or oil pressure safety switch opened. After the 4th failed restart, A3 is shown.

Causes the manufacturer lists

  • Refrigerant charge or type
  • Low pressure switch setting or wiring
  • Iced coil
  • Condenser fans or dirty condenser coil
  • Head pressure controls
  • Oil level
  • Compressor module or phase loss monitor

What staff can safely check

  • Make sure nothing is blocking airflow around the outdoor condensing unit
E9

Communication wiring error

Technician

Communication between linked (master/slave) evaporator boards was lost after first connecting.

Causes the manufacturer lists

  • Board has no 24V power
  • Crossed or broken communication wiring
888

Low supply voltage

Technician

Board supply voltage is below 18V, usually seen at first power-up.

Causes the manufacturer lists

  • Transformer, wiring or board voltage problem

Seeing Heatcraft codes you can't clear?

Same- or next-day appointments across the Denver metro. Written quote before any work, EPA 608 certified technicians.

Request service

Model notes

Normal status displays (not faults): oFF, Coo (cooling), Pdn (pumpdown), dEF (defrost), drn (draining), dLY (delay), tSt (test), SEr (service), Loc/UnL. E8 is not defined in the manual.

Sources

Compiled and paraphrased from the manufacturer documents above. Codes differ between model years and control boards — confirm against the manual for your exact model. ABC Denver Appliance Repair is an independent service company, not affiliated with Heatcraft.

From our job records

Photos from our job records

Real photos our technicians took on calls around Denver and the Front Range. Each caption says what was done; no customer details are shown.

Gas range in Aurora after an oven igniter replacement
Gas range in Aurora after an oven igniter replacement
Frigidaire washer after the lock replacement
Frigidaire washer after the lock replacement
Freezer drawer temperature check after a control board replacement, Greenwood Village
Freezer drawer temperature check after a control board replacement, Greenwood Village
Maytag washer in Wheat Ridge after a water valve replacement
Maytag washer in Wheat Ridge after a water valve replacement

Call (720) 534-0432