A1
High box temperature
Status / staff can check Room temperature stayed above the high alarm setpoint for the alarm time (default 60 minutes). Not checked during defrost.
What staff can safely check
- Make sure the walk-in door closes and seals fully
- Check strip curtains and that the door isn't propped open
A2
Low box temperature
Technician Room temperature stayed below the low alarm setpoint for the alarm time.
What staff can safely check
- Check product for freezing
A3
System start-up failure
Technician The compressor failed to start after 4 attempts (it retries every 4 minutes and keeps trying).
Causes the manufacturer lists
- Pressure safety switch (high, low or oil) open - see E7
What staff can safely check
- Move product if the box is warming
A4
Input fault
Technician Box temperature sensor, suction temperature sensor or pressure transducer is open or not installed.
Causes the manufacturer lists
- Faulty sensor or transducer
E1
Room temperature sensor fault
Technician Room sensor is shorted, open or not installed. The system pumps down and stays off until the fault is cleared.
Causes the manufacturer lists
- Sensor or its board connection
What staff can safely check
- Move product to other refrigeration
E2
Defrost temperature sensor fault
Technician Defrost sensor is shorted, open or not installed.
Causes the manufacturer lists
- Sensor or its board connection
E3
Suction temperature sensor fault
Technician Suction temperature sensor is shorted, open or not installed. System pumps down and stays off.
Causes the manufacturer lists
- Sensor or its board connection
E4
Suction pressure transducer fault
Technician Suction pressure transducer is shorted, open or not installed. System pumps down and stays off.
Causes the manufacturer lists
- Transducer or its board connection
E5
Outdoor temperature sensor fault
Technician Outdoor temperature sensor is shorted.
Causes the manufacturer lists
E6
Low superheat
Technician Superheat stayed at 0°F for 2 minutes during cooling.
Causes the manufacturer lists
- Wrong refrigerant setting on board
- Iced coil / defrost problem
- Expansion valve (EEV) problem
- Low pressure switch setting
- Sensor or transducer reading wrong
What staff can safely check
- Report any heavy ice build-up on the evaporator coil
E7
Compressor shutdown
Technician A high-pressure, low-pressure or oil pressure safety switch opened. After the 4th failed restart, A3 is shown.
Causes the manufacturer lists
- Refrigerant charge or type
- Low pressure switch setting or wiring
- Iced coil
- Condenser fans or dirty condenser coil
- Head pressure controls
- Oil level
- Compressor module or phase loss monitor
What staff can safely check
- Make sure nothing is blocking airflow around the outdoor condensing unit
E9
Communication wiring error
Technician Communication between linked (master/slave) evaporator boards was lost after first connecting.
Causes the manufacturer lists
- Board has no 24V power
- Crossed or broken communication wiring
888
Low supply voltage
Technician Board supply voltage is below 18V, usually seen at first power-up.
Causes the manufacturer lists
- Transformer, wiring or board voltage problem