Box Temp
TechnicianBox temperature sensor fault.
Causes the manufacturer lists
- Sensor or its connections
Home / Error codes / Heatcraft
Walk-in refrigeration · 27 codesWalk-in cooler and freezer evaporators with the intelliGen Refrigeration Controller. Covers: intelliGen iRC (2023 manual)
The OLED display shows the active ER (error), AL (alarm) or IN (information) code. The light bar turns yellow for an error and red for an alarm; the affected unit flashes.
The manual does not describe an acknowledge or reset procedure; it mentions clearing alarm history in the alarm menu.
If the same code comes back after a reset, stop resetting it — repeated restarts can hide the real fault or damage components. Call a technician.
Box temperature sensor fault.
Causes the manufacturer lists
Coil temperature sensor fault.
Causes the manufacturer lists
Evaporator suction temperature sensor fault.
Causes the manufacturer lists
Suction pressure transducer fault.
Causes the manufacturer lists
Control circuit fault (only when a condensing unit is wired to the board); the troubleshooting guide relates it to safety trips.
Causes the manufacturer lists
Board supply voltage fell below 18 VAC; the system may shut down and restart after power is restored.
Causes the manufacturer lists
Board supply voltage is high.
Unit ran 2 minutes below the low superheat setpoint; can occur during initial start-up.
Clock battery issue; time needs to be set.
Causes the manufacturer lists
User interface (display) failure.
Causes the manufacturer lists
Humidity sensor reading is high.
What staff can safely check
Humidity sensor reading is low.
Humidity sensor fault.
Lead-lag connection to another system lost.
Refrigerant leak detected below the mitigation level.
Causes the manufacturer lists
What staff can safely check
Refrigerant leak detection sensor fault.
Leak detection sensor needs service.
Leak detection mitigation condition.
Causes the manufacturer lists
What staff can safely check
Communication lost with the leak mitigation controller.
Box temperature above the high alarm setpoint after the alarm delay (default 60 min); delayed further if the door was recently open a lot.
What staff can safely check
Box temperature below the low alarm setpoint after the alarm delay.
System start-up alarm (only when a condensing unit is wired).
Triggered by sensor errors ER01, ER03 or ER04.
Door open longer than the door alarm time (default 60 min).
Causes the manufacturer lists
What staff can safely check
Leak mitigation mode is active: the shut-off valve closes and fans run.
Causes the manufacturer lists
What staff can safely check
Defrost ended in under 5 minutes 8 times in a row.
Defrost ended on time (not temperature) 8 times in a row.
What staff can safely check
Same- or next-day appointments across the Denver metro. Written quote before any work, EPA 608 certified technicians.
Codes listed by name only in the manual without further detail were omitted (ER13, ER18, ER20, ER23-26, ER36, AL10, AL11). URL contains spaces; encode as %20 if linking.
Compiled and paraphrased from the manufacturer documents above. Codes differ between model years and control boards — confirm against the manual for your exact model. ABC Denver Appliance Repair is an independent service company, not affiliated with Heatcraft.
Real photos our technicians took on calls around Denver and the Front Range. Each caption says what was done; no customer details are shown.